illuminating technologies for life
Home
Information Specifications Manuals
Warranty Literature Parts
Information Specifications Manuals Warranty Literature Parts
DISINFECTION HOT WATER LOW UVT TOC
Low UVT
Low UVT
LUMINOR EQUIPMENT SPECIFICATIONS
RAINIER-505.0, Light Commercial Amalgam UV Systems, non-monitored
MODEL LR5-355-50 LR5-555-50 LR5-855-50 LR5-1105-50 LR5-1405-50 LR5-1755-50
Flow Rate
30 mJ/cm² @ 50%
UVT (Industry Std.)
14 gpm 23 gpm 35 gpm 36 gpm 45 gpm 51 gpm
53 lpm 87 lpm 133 lpm 136 lpm 170 lpm 193 lpm
3.2 m³/hr 5.2 m³/hr 8.0 m³/hr 8.2 m³/hr 10.2 m³/hr 11.6 m³/hr
Electrical 230V / 50-60Hz
(IEC power cords required)
Plug Type North American NEMA 6/15: "5" suffix
European CEE 7/7: "2" suffix
British BS1363: "3" suffix"
Australian AS/NZ 3112: "4" suffix
Lamp Watts 104 152 207 304 344 414
Power (watts) 120 170 220 320 360 430
Replacement Lamp RL-500A RL-720A RL-1000A RL-720A
(2 required)
RL-843A
(2 required)
RL-1000A
(2 required)
Replacement Sleeve RQ-500 RQ-720 RQ-1000 RQ-720
(2 required)
RQ-843
(2 required)
RQ-1000
(2 required)
Chamber Material 316L Stainless Steel, A249 Pressure Rated Tubing, Polished & Passivated
Reactor Dimensions 4x27.2x5.6"
10x69x14cm
4x35.8x5.6"
10x91x14cm
4x46.8x5.6"
10x119x14cm
6x35.8x7.9"
15x91x20cm
6x40.6x7.9"
15x103x20cm
6x46.8x7.9"
15x119x20cm
Controller Dimensions 11.8 x 7.9 x 6.3" (30.0 x 20.1 x 16.0 cm)
Maximum Operating Pressure 10.3 bar (150 psi)
Operating Temperature Range 2-40° C (36-104° F)
UV Monitor Upgradeable, includes visual glow plug
Remote-On Yes
Dry Contacts (solenoid ready) Optional
4-20 mA Output Optional
Lamp Age Counter Yes
Lamp-Out Indicator (audible & visual) Yes
*Note: based on flow velocity of 8.2 ft/s (2.5 m/s), flow rates are limited by port sizes:
1½": 52gpm (197 lpm)
2": 85.8gpm (325 lpm)
2½": 122.4 gpm (463 lpm)
3": 189 gpm (715 lpm)
4": 325.4 gpm (1232 lpm)